Skip to main content
Gas chromatograph in an analytical laboratory

Know-how: hydrogen in the lab

Cylinder or generator? What matters is the amount.

Hydrogen is the preferred fuel gas for the FID and increasingly the carrier gas in GC as well. It is also the most easily ignited gas in the lab. How dangerous it becomes depends on how much of it is on hand. A cylinder keeps several cubic metres in stock at high pressure. A SCHMIDLIN hydrogen generator produces only what your GC needs right now.

4–77 vol%explosive range in air
0.017 mJminimum ignition energy
9–12.5 m³H₂ in a 50 L cylinder (200–300 bar)
max. 81 L/hfrom our largest H₂ generator (NM Plus)

Same gas, different risk

The same hydrogen. The generator keeps it under control.

Hydrogen is the most easily ignited gas in the lab, whether it comes from a cylinder or a generator. The difference lies in how much of it is on hand and at what pressure.

A cylinder keeps several cubic metres at 200 to 300 bar in the room. A SCHMIDLIN hydrogen generator holds no stock. It produces exactly the gas your GC needs right now, at no more than 11 bar, and shuts itself down on a leak.

Property of H₂From a cylinderFrom a generator
Explosive range 4–77 vol%A single failure can release the entire stock, far beyond the explosive limit.No more than the rated output can flow, so the concentration in the room stays far below the explosive limit.
Minimum ignition energy 0.017 mJA small spark during a cylinder change or at a fitting is enough.No cylinder changes, no high-pressure fittings in the lab.
Colourless and odourlessA leak at the valve or regulator goes unnoticed until a gas warning system responds.Integrated sensors detect internal and external leaks and shut the generator down.
14 times lighter than airAn escaping stock collects under the ceiling.Small amounts quickly dilute in the room air.
Warms up on expansionWhen gas escapes at 200 to 300 bar, the jet can ignite without an external ignition source.No more than 11 bar outlet pressure.
Invisible flameA fire at the cylinder valve is barely visible in daylight.Without a stock there is no gas source to keep it burning.

Substance data from the GESTIS database. Instrument data from the data sheets of the VICI DBS hydrogen generators.

The decisive factor

How much hydrogen can escape in your lab?

A cylinder is a stock: if it fails, its entire content can escape. A generator only produces hydrogen on demand. Even in the worst case it delivers no more than its cell can produce per hour.

50 L cylinder, 200–300 bar9,000–12,500 L stock
10 L cylinder, 200 bar≈ 1,800 L stock
NM Plus hydrogen generator, full loadmax. 81 L per hour

For comparison: a 50 m³ lab reaches the lower explosive limit at 4 vol% hydrogen, i.e. about 2,000 L.

SourceCan escapeConcentration in the room
50 L cylinder9–12.5 m³ at once≈ 16–22 vol%, four to five times the lower explosive limit
10 L cylinder≈ 1.8 m³ at once≈ 3.5 vol%, above the explosive limit under the ceiling
NM Plus generatormax. 81 L per hour≈ 0.16 vol%, about 4 % of the lower explosive limit

Rough calculation: 50 m³ room, complete mixing. For the generator, one air change per hour and the worst case that it keeps running at full output despite a leak. In reality it shuts down on a leak, and labs with mechanical ventilation usually have a much higher air change rate. In practice the generator value is therefore even lower.

Stock versus supply

The cylinder runs empty. The generator keeps delivering.

Sooner or later a cylinder is empty and has to be changed. At full load the NM Plus delivers 81 litres per hour, day and night. After 22 hours it has produced as much hydrogen as a 10 L cylinder holds, after 4.6 to 6.4 days the content of a 50 L cylinder. It even produces the content of a bundle of twelve 50 L cylinders (107 to 151 m³) in 55 to 78 days, without outdoor storage, piping or bundle changes. And there is never a stock in the lab.

Chart: hydrogen in litres over 8 days. 50 L cylinder with 9,000 to 12,500 L (200 to 300 bar) and 10 L cylinder with 1,800 L as a fixed stock; the NM Plus delivers 81 L per hour and overtakes the 10 L cylinder after 22 hours and the 50 L cylinder after 4.6 to 6.4 days.

Inside the instrument

Where the cylinder becomes a risk in GC and GC-MS.

Leak in the column oven

If a capillary column breaks or a fitting comes loose, hydrogen flows into the closed oven. According to Shimadzu, 40 mL/min into 15 litres reaches the lower explosive limit after 15 minutes. At 500 mL/min, a 40-litre oven gets there in just over three minutes. With a generator, no high-pressure stock keeps flowing, and it shuts down on a leak.

Power failure at the GC-MS

Agilent warns: if the power fails, GC and MS stop, but the cylinder keeps supplying gas. Hydrogen can accumulate in the vacuum system and explode when the pumps restart automatically. A generator without power produces no more hydrogen.

Shut-off at the source

According to the manufacturer, VICI DBS hydrogen generators shut down automatically on an internal or external leak, overpressure and low water. An oven or room sensor can also cut the generator's power. A cylinder needs its own shut-off valve for this.

What matters is how much can keep flowing behind the GC: several cubic metres from a cylinder, no more than the rated output from a generator. And on a leak, it shuts down.

Regulations

The requirements a cylinder brings. And what a generator removes.

In Germany, hydrogen in the lab is governed mainly by the Hazardous Substances Ordinance, the Industrial Safety Regulation, TRGS 526 “Laboratories”, TRGS 510 on storage and DGUV Rule 113-001 on explosion protection.

TopicHydrogen gas cylinderHydrogen generator
LocationUnder TRGS 526, generally outside the lab, with gas supplied through permanently installed lines. Inside the lab only as an exception and with the smallest possible container.Sits right next to the instrument or in the lab. No compressed gas is stored.
Storage in the workroomUnder TRGS 510, only in safety cabinets (G30 to G90 per EN 14470-2) with mechanical exhaust to the outside.No compressed gas container, so no storage of compressed gas.
Explosion protectionDuring withdrawal, at least 120 air changes per hour in the cabinet so that no Ex zone forms there. Otherwise Zone 2 with explosion-protected equipment.The risk assessment starts from a small, limited release rate instead of several cubic metres in stock.
InspectionsVentilation and gas warning systems every year, the explosion-protected installation at least every six years (German BetrSichV, Annex 2, Section 3).No inspections for a gas cylinder cabinet and its exhaust. SCHMIDLIN service handles maintenance, the Smart Box monitors the condition.
HandlingTransport with protective cap and cylinder trolley, secured against falling, leak test at every cylinder change, never run completely empty.No cylinder changes. Just top up deionized water.
Pressure200 to 300 bar in the container.No more than 11 bar outlet pressure.

General information, not legal advice. The current version of the rules and the operator's risk assessment are what count.

Making the switch

What a SCHMIDLIN generator changes in your lab.

Less gas in the room

Instead of several cubic metres in stock, only the gas your GC needs right now is present. The risk shrinks by orders of magnitude.

Simpler assessment

Your risk assessment works with a small, limited release rate instead of a high-pressure stock. The gas cylinder cabinet and the inspection of its exhaust are no longer needed.

No cylinder handling

No moving heavy cylinders, no changes in the middle of a sequence, no leak test after every connection. Just top up deionized water.

Monitored around the clock

The SCHMIDLIN Smart Box reports anomalies to our service team, often before anyone in the lab notices. We plan maintenance according to the actual condition.

Cascade up to ten units

As your demand grows, connect up to ten NM Plus in parallel. You get more output and built-in redundancy: while one unit is being serviced, the others keep supplying your GCs. You still need no gas stock.

Consistent purity

Up to 99.99996 % hydrogen, day after day. No air or moisture entering during cylinder changes and no variation from batch to batch.

For your safety officer

The data for your risk assessment.

Whether a switch to a generator succeeds often depends on the safety officer. We compile the information they need: the instrument's maximum hydrogen flow, shut-off functions, outlet pressure and an example calculation for your room. That makes the assessment quick.

Request instrument data
  1. Tell us about room and instrumentsRoom size, ventilation and the GCs that need hydrogen.
  2. Choose the generatorWe size the right generator with headroom.
  3. Receive the dataData sheet, shut-off logic and example calculation for your records.

Frequently asked questions

Hydrogen in the lab: the key questions.

Your question is not listed? Get in touch.

  • Is a hydrogen generator safer than a cylinder?

    It reduces the biggest risk: the amount that can escape at once. A 50 L cylinder holds 9 to 12.5 m³ of hydrogen at 200 to 300 bar. A generator produces the gas on demand at no more than 11 bar and shuts down on a leak, overpressure or power failure.

  • Does a generator make the risk assessment simpler?

    Yes. It no longer has to account for a high-pressure stock of several cubic metres, only for a small, limited release rate. The gas cylinder cabinet with exhaust, cylinder changes and the related inspections no longer apply. We supply your safety officer with the instrument data.

  • Can I use hydrogen as carrier gas instead of helium?

    Yes, and many labs do because of shorter run times and helium shortages. Hydrogen is then also present in the injector, the column and, where applicable, the mass spectrometer. That is exactly when a generator is the better source: it delivers consistent purity up to 99.99996 % and shuts down on a power failure instead of continuing to flood the MS. We size the generator for carrier and fuel gas together with you.

  • What if one generator is not enough for my lab?

    One NM Plus supplies up to 33 GCs with up to 1350 mL/min. If you need more, cascade up to ten generators. They work as one system and back each other up: if one unit fails or is being serviced, the others keep delivering. Your supply grows with your lab without adding a high-pressure stock.

  • How much effort does running a generator take?

    Very little. You top up deionized water, and our service team handles maintenance on site in Germany and Austria. With the SCHMIDLIN Smart Box we spot anomalies early and plan maintenance according to the actual condition.

  • What happens during a power failure?

    Without power there is no electrolysis, so the generator stops producing hydrogen. A cylinder, by contrast, keeps supplying gas as long as the valve is open. Agilent therefore recommends closing the hydrogen source after a power failure before the MS pumps down again.

Less hydrogen in the room. More peace of mind in the lab.

We will show you what a SCHMIDLIN generator saves in your lab in safety equipment, inspections and cylinder logistics.

or by email to info@schmidlin-labor.de